一、目的確保低壓配(pei)電柜和(he)各設備控(kong)制柜的正(zheng)常安全運(yun)行。


二、范圍適合低壓配(pei)電室配(pei)電柜(ju),各設備的控(kong)制柜(ju)視具體情況參照有(you)關(guan)條(tiao)款(kuan)執行。


三(san)、職責由機電安裝維修工(gong)程部維修組(zu)每半年(nian)對其(qi)進行一次全(quan)面檢查保養,并以較(jiao)短的停電時間完成保養工(gong)作。

四、內容


1、準備工作:


A、在(zai)配電(dian)柜停電(dian)保養的前一天通(tong)知住戶停電(dian)起(qi)止時間。


B、停(ting)電前做好一(yi)切準備(bei)工作,特(te)別(bie)是工具(ju)的準備(bei)應齊全;并以(yi)較短的停(ting)電時間完成保養工作。


2、保養程序:


A、實行分(fen)段保(bao)(bao)(bao)養(yang),先保(bao)(bao)(bao)養(yang)保(bao)(bao)(bao)安負荷段。


B、停保安負荷電(dian)(dian)(dian),其余負荷照常供市(shi)電(dian)(dian)(dian)。斷(duan)開(kai)供保安負荷市(shi)電(dian)(dian)(dian)的空(kong)氣(qi)開(kai)關,斷(duan)開(kai)發(fa)電(dian)(dian)(dian)機(ji)空(kong)氣(qi)開(kai)關,把發(fa)電(dian)(dian)(dian)機(ji)選擇開(kai)關置于停止位置,拆開(kai)蓄電(dian)(dian)(dian)池(chi)正、負極(ji)線(xian),掛標示牌,以(yi)防發(fa)電(dian)(dian)(dian)機(ji)發(fa)送電(dian)(dian)(dian)。


C、檢查母(mu)線接頭(tou)處有無變形,有無放電變黑痕跡,緊固聯(lian)接螺(luo)栓,螺(luo)栓若有生銹應(ying)予更換,確保接頭(tou)連接緊密。檢查母(mu)上的絕緣有無松動和損(sun)壞。


D、用(yong)手柄把(ba)總空氣從配(pei)電(dian)柜(ju)中搖(yao)出,檢(jian)查主(zhu)觸(chu)點是否(fou)有燒溶痕跡,檢(jian)查滅弧罩(zhao)是否(fou)燒黑(hei)和損壞,緊固各(ge)接線螺(luo)絲、清潔柜(ju)內(nei)灰塵,試驗機械的合(he)閘、分閘情況


E、把(ba)各分開關柜從抽屜(ti)柜中取出(chu),緊固各接線(xian)端子。檢(jian)查電流(liu)互(hu)感器、電流(liu)表、電度表的(de)安裝(zhuang)和(he)接線(xian),檢(jian)查手柄操作機構的(de)靈活可靠性(xing),緊固空氣(qi)開關進(jin)出(chu)線(xian),清潔開關柜內和(he)配(pei)電柜后面引出(chu)線(xian)處的(de)灰(hui)塵。


F、保養(yang)電(dian)(dian)(dian)(dian)容柜時,應(ying)先(xian)斷開電(dian)(dian)(dian)(dian)容器總開關,用(yong)10MM2以上的導線把電(dian)(dian)(dian)(dian)容器逐個對地放(fang)電(dian)(dian)(dian)(dian),然后檢(jian)查接觸器、電(dian)(dian)(dian)(dian)容器接線螺絲、接地裝置是(shi)否良好,檢(jian)查電(dian)(dian)(dian)(dian)容器有無脹肚現象,并用(yong)吸塵器清潔柜內灰塵。


G、保安負(fu)荷段(duan)保養完畢,可起動(dong)發電(dian)機對其供電(dian)、停市電(dian)保養母線(xian)段(duan)。


H、逐(zhu)級(ji)斷開(kai)(kai)低壓(ya)側空(kong)氣開(kai)(kai)關,然(ran)后斷開(kai)(kai)供變壓(ya)器(qi)電(dian)的高壓(ya)側真空(kong)斷路器(qi),合(he)上接地開(kai)(kai)關,懸掛“禁止合(he)閘,有人工作”標示(shi)牌。


I、按C、D、E、F項所有要(yao)求保養完畢(bi)配電(dian)(dian)(dian)柜后,拆除安全裝(zhuang)置,斷(duan)開高壓側(ce)接(jie)地(di)開關,合(he)上真空(kong)斷(duan)路器,觀察變壓器投入運行無誤后,向低(di)壓配電(dian)(dian)(dian)柜逐級送電(dian)(dian)(dian),并把保安負荷由發電(dian)(dian)(dian)機供電(dian)(dian)(dian)轉為市電(dian)(dian)(dian)供電(dian)(dian)(dian)。



五(wu)、安全注意(yi)事項


1、停電(dian)后應驗電(dian)。


2、在(zai)分段保養(yang)配電柜時,帶(dai)電和不帶(dai)電配電柜交界處應裝設隔離裝置。


3、操作(zuo)高壓側真空(kong)斷路器時,應穿絕緣(yuan)靴(xue),戴絕緣(yuan)手套,并有專人(ren)監(jian)護。


4、保養電(dian)(dian)容(rong)器柜時(shi),在電(dian)(dian)容(rong)器對地(di)放電(dian)(dian)之前,嚴禁觸摸(mo)。


5、保(bao)養完畢送電前,應先檢查有無工具遺留在配電柜內(nei)。



六、相關文件及(ji)記錄


1、檢修工作票;


2、配(pei)電柜、控(kong)制(zhi)柜年保養記錄(lu);


3、設(she)備維修記錄。